ABCB Housing Provisions
Search the National Construction Code editions
13.2
NT Part 13.2 Building fabricNT Part 13.2 Building fabric
must have a thermal break, consisting of a material with an R-Value of not less than 0.2, installed between the metal sheet roofing and its supporting member.
Climate zone 1 | Climate zone 3 | ||
---|---|---|---|
Tiled roof (clay or concrete) | Total R-Value of roof and ceiling materials | 0.43 | 0.37 |
Minimum value of added R-Value of insulation | 2.27 | 2.33 | |
Metal roof | Total R-Value of roof and ceiling materials | 0.41 | 0.35 |
Minimum value of added R-Value of insulation | 2.29 | 2.35 | |
Minimum required Total R-Value | 2.70 | 2.70 |
Climate zone 1 | Climate zone 3 | ||
---|---|---|---|
Tiled roof (clay or concrete) | Total R-Value of roof and ceiling materials | 0.73 | 0.22 |
Minimum value of added R-Value of insulation | 1.97 | 2.48 | |
Metal roof | Total R-Value of roof and ceiling materials | 0.71 | 0.20 |
Minimum value of added R-Value of insulation | 1.99 | 2.50 | |
Minimum required Total R-Value | 2.70 | 2.70 |
Climate zone 1 | Climate zone 3 | ||
---|---|---|---|
Tiled roof (clay or concrete) | Total R-Value of roof and ceiling materials | 0.55 | 0.40 |
Minimum value of added R-Value of insulation | 2.15 | 2.30 | |
Metal roof | Total R-Value of roof and ceiling materials | 0.53 | 0.38 |
Minimum value of added R-Value of insulation | 2.17 | 2.32 | |
Minimum required Total R-Value | 2.70 | 2.70 |
Percentage of ceiling area uninsulated | Minimum R-Value of ceiling insulation required to satisfy 13.2.3(1) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
1.0 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 4.5 | 5.0 | 5.5 | |
0.5% to less than 1.0% | 1.0 | 1.6 | 2.2 | 2.8 | 3.4 | 4.0 | 4.7 | 5.4 | 6.2 | 6.9 |
1.0% to less than 1.5% | 1.1 | 1.7 | 2.3 | 2.9 | 3.6 | 4.4 | 5.2 | 6.1 | 7.0 | X |
1.5% to less than 2.0% | 1.1 | 1.7 | 2.4 | 3.1 | 3.9 | 4.8 | 5.8 | 6.8 | X | X |
2.0% to less than 2.5% | 1.1 | 1.8 | 2.5 | 3.3 | 4.2 | 5.3 | 6.5 | X | X | X |
2.5% to less than 3.0% | 1.2 | 1.9 | 2.6 | 3.6 | 4.6 | 5.9 | X | X | X | X |
3.0% to less than 4.0% | 1.2 | 2.0 | 3.0 | 4.2 | 5.7 | X | X | X | X | X |
4.0% to less than 5.0% | 1.3 | 2.2 | 3.4 | 5.0 | X | X | X | X | X | X |
When considering the reduction of insulation because of exhaust fans and recessed downlights, 1% of the ceiling area for a 200 m2 sized house would permit 2 bathroom heater-light assemblies, a laundry exhaust fan, a kitchen exhaust fan and either approximately 25 recessed downlights with 100 mm clearance to the insulation or approximately 10 recessed downlights with 200 mm clearance to the insulation.
Roof lights serving a habitable room or an interconnecting space such as a corridor, hallway, stairway or the like—
Roof light shaft index | Total area of roof lights serving the room or space as a percentage of the floor area of the room or space | |
---|---|---|
Up to 5% of the floor area of the room or space | More than 5% and up to 10% | |
Less than 0.5 | SHGC of not more than 0.5 and a Total U-Value of not more than 5.0 | SHGC of not more than 0.25 and a Total U-Value of not more than 2.5 |
1.0 to 2.5 | Total U-Value of not more than 5.0 | SHGC of not more than 0.25 and a Total U-Value of not more than 2.5 |
2.5 and above | Total U-Value of not more than 5.0 | SHGC of not more than 0.25 and a Total U-Value of not more than 2.5 |
Guttering can be considered as providing shading if attached to a shading projection.
Walls with a surface density of 220 kg/m2 or more are deemed to achieve acceptable levels of thermal performance due to their ability to store heat and therefore slow the heat transfer through the building fabric. These walls are defined by surface density (kg/m2), which is the mass of one vertical square metre of wall, in order to reduce the complexity when measuring the mass of walls with voids.
The following are examples of some typical wall constructions that achieve a surface density of 220 kg/m2:
A Class 10a building attached to a Class 1 building must—
The attachment of a Class 10a building, such as a garage, glasshouse, solarium, pool enclosure or the like should not compromise the thermal performance of the Class 1 building. In addition, the Class 10a building may be insulated and so assist the Class 1 building achieve the required thermal performance. Explanatory Figure NT 13.2.6 below depicts examples of a Class 1 building with an attached Class 10a garage.
In (a), the thermal performance required for the Class 1 building may be achieved by the outside walls and floor of the Class 10a garage.
In (b), the thermal performance required for the Class 1 building may be achieved by the walls and floor of the Class 1 building as if the Class 10a garage is an under floor space with an enclosed perimeter.