Specification 44 Calculation of heating load limit, cooling load limit and thermal energy load limit
Archive Number
State variations
The heating load limit of a space, measured in MJ/m2.annum, is equal to the greater of—
- 4; and
-
, where—
-
= the total annual heating degree hours of the building location; and
-
= the area adjustment factor for the heating load limit, determined in accordance with Table S44C2.
Table S44C2 Area adjustment factors for the heating load limit
| Total area of habitable rooms (AH) |
Area adjustment factor (FH) |
| ≤ 50 m2 |
1.37 |
| > 50 m2 to ≤ 350 m2 |
|
| > 350 m2 |
0.84 |
Archive Number
State variations
(1) The cooling load limit of a space, measured in MJ/m2.annum, is calculated in accordance with the following formula:
(2) In the formula at (1)—
-
= the cooling load limit (MJ/m2.annum); and
-
= the total annual cooling degree hours of the building location; and
-
= the total annual dehumidification gram hours of the building location; and
-
= the area adjustment factor for the cooling load limit, determined in accordance with Table S44C3.
Table S44C3 Area adjustment factors for the cooling load limit
| Total area of the habitable rooms (AH) |
Area adjustment factor (FC) |
| ≤ 50 m2 |
1.34 |
| > 50 m2 and ≤ 200 m2 |
|
| > 200 m2 and ≤ 1000 m2 |
|
| > 1000 m2 |
0.71 |
Archive Number
State variations
Thermal energy load limit
(1) The thermal energy load limit of a space, measured in MJ/m2.annum, is calculated in accordance with the following formula:
(2) In the formula at (1)—
-
= the thermal energy load limit; and
-
= the heating load limit; and
-
= the cooling load limit; and
-
= the annual average daily outdoor temperature range.